Stay informed! Visit the SA Department of Health's website for COVID-19 updates: www.sacoronavirus.co.za

Affinity Must Power
a BBBEE Company

EH9335 Series (20KVA-80KVA)

CATEGORIES: UPS

EH9335 Pro series three phase UPS adopts double conversion online design. Having input power factor correction (PFC) to make the input power factor up to 0.99. Having high energy density ratio to greatly reduces its own volume and room space. Adopting digital control, the system has high stability and self-protection and fault diagnosis capabilities. This UPS series can solve power problems much better, such as voltage instantaneous drop, amplitude reduction, high voltage pulse, surge voltage, harmonic distortion, clutter interference, and frequency fluctuation.

FEATURES

  • Parallel Redundancy
  • Output load capacity
  • Adaptive load three-phase unbalance
  • Double conversion high frequency online design
  • RS232,RS485 communication interface, parallel cover and SNMP card (optional )
  • Maintenance bypass switch


Model EH9335-20KS EH9335-30KS EH9335-40KS EH9335-60KS EH9335-80KS
CAPACITY 20KVA \ 18KW 30KVA \ 27KW 40KVA \ 32KW 60KVA \ 54KW 80KVA \ 64KW
INPUT
Input Phase 3PH 4W +G
Voltage 380VAC
Voltage Range 208~478Vac
Frequency Range 45-55Hz at 50Hz \ 54-66Hz at 60Hz (auto adaptation )
Power Factor ≥0.99
THDi ≤3% (100% non-linear load )
Bypass range Bypass protection voltage upper limit: 220V: + 25% (optional: +10% \ +15% \ +20%); 230V: + 20% (optional: +10% \ 15%); 240V: + 15% (optional: +10%);
Bypass protection voltage lower limit: -45% (optional:-20% \ -30%)
Bypass frequency protection range: ±10%
OUTPUT
Output phase (3PH 4W +G) or (1PH + N)
Voltage Range 380 \ 400 \ 415VAC or 220 \ 230 \ 240VAC
Voltage stabilizing accuracy ±1%
Frequency Range AC mode: ±1% \ ±2% \ ±4% \ ±5% \ ±10% setting (50\60±0.2)Hz Battery Mode: (50\60±0.2%)Hz
Load peak ratio 3:1
Output voltage distortion ≤2% (linear load), ≤5% (non-linear load)
BATTERY
Battery voltage Optional:DC±192V \ ±204 \ ±216V \ ±228 \ ±240V (±16 \ 17 \ 18 \ 19 \ 20)
Charge current 10A max
OTHER
Transfer time AC mode tranfer to bypass mode: 0ms ; AC mode transfer to battery mode: 0ms
Efficiency Normal mode ≥ 94.5%
Communication interface USB,RS485,Dry contact, Parallel card(optional ) SNMP card (optional )
Standar YD/T1095-2008
PROTECTION
Overlond capacity Normal mode: ≤ 110% for 10 mins, ≤ 125% for 1 mins, ≥ 150% shut down
Over temperature Mormal mode :transfer to bypass mode   Battery model : shut down
EPO Shut down
WORK ENVIR
Temperature 0°C ~ 40°C
Storage temperature -25°C - 55°C
Relative humidity 0~95% (non condensing )
Altitude < 1500m, (with derating ≥1500m )
PHYSICAL
Machine dimension (DxWxH) 724X250X734mm 805X335X978mm
Net weight (kg) 45 46 48 80.5 82.5